sk
Kategórie
Zobrazené produkty

Fluke Norma 5000 Fluke VR1710 - Záznamník kvality elektrickej energie Fluke 43B - Jednofázový analyzátor kvality el. energie Fluke 345 - Kliešťový merač kvality elektrickej energie

Fluke 1750 a Fluke-1750/B - Three-Phase Power Quality Recorder

Fluke 1750 a Fluke-1750/B - Three-Phase Power Quality Recorder

Cena: na požiadanie


Poslať známemu


Record three-phase power quality and monitor for power quality disturbances with the new Fluke 1750 Power Recorder and the Fluke Power Analyze software. These power meters automatically record every power quality parameter and event, on every cycle – all the time.

Applications
Long-term analysis: Uncover hard-to-find or intermittent issues
Power quality surveys: Quantify power quality throughout a facility, documenting results with professional reports
Quality of service compliance: Validate incoming power quality at the service entrance
Semi-permanent monitoring: Monitor critical equipment, capturing power quality events to correlate with equipment malfunctions

Premium accuracy and measurementtechniques: Guaranteed for all power quality parameters, with IEC 61000-4-30 Class A measurement systems
Quick and reliable configuration: PDA wireless “front panel interface” provides a window into what the instrument is recording, enabling quick and reliable configuration even in awkward test locations
Threshold-free set up: Apply thresholds after data is collected with Fluke Power Analyze Software
Captures everything: Cross-channel and current triggering capture every measurement, on every channel, every time
Intuitive PC software: Easily analyze data and generate reports
Plug and play: Set up in minutes with self-identifying current probes and single-lead voltage connections
No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct
Measure every parameter: Voltage and current on three phases, neutral, and ground
5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
Quickly retrieve data: With included SD memory card or via the 100BaseT high-speed Ethernet connection



Includes
1750 acquisition unit
PDA wireless “front panel interface” and charger power plug adapters
4 - 400A current probes (3140)
5 Test leads and clips
SD memory card
Fluke Power View and Fluke Power Analyze software
Power cord with international plug set
Ethernet cable
Color localization set
Printed Getting Started manual
Product CD with software and user manual PDF
CS 1750/1760 Rugged transit softcase


Optional Accessories:


Flexible Current Transformers
3110-PR - 100 AMP FLEX CT 24 IN. 100 Amp Flexi-CT, 2 - 100 amps flexible current transformer, 24“ long.
3210-PR - 1000 AMP FLEX CT 24 IN. 1000 Amp Flexi-CT, 20 - 1000 amps flexible current transformer, 24” long.
3310-PR - 5000 AMP FLEX CT 24 IN. 5000 Amp Flexi-CT, 100 - 5000 amps flexible current transformer, 24” long.
3312-PR - 5000 AMP FLEX CT 48 IN. 5000 Amp Flexi-CT, 100 – 5000 amps flexible current transformer, 48” long.

Clamp-on Current Transformers
3005-PR - 5 AMP CLAMP W/3570 CT CABLE. 0.1 - 5 amps clamp-on current transformer with 10’ Extender cable for Power Recorder.  Jaw opening 0.78”, 20mm.
3014-PR - 40 AMP CLAMP. 0.1 - 40 amps clamp-on current transformer with 10’ Extender cable for Power Recorder.  Jaw opening 0.78”, 20mm.
3140R - 400 AMP CLAMP. 2 - 400 amps clamp-on current transformer with 8' cable for Power Recorder.  Jaw opening 1.25", 32mm

Miscellaneous Accessories
FLUKE-1750/SEAT-L - Fluke Power Analyze - Additional SEAT LICENSE.  One additional license for installation on one additional PC
FLUKE-1750/SITE-L - Fluke Power Analyze - Additional SITE LICENSE. Site license for installation on unlimited PCs
FLUKE-1750/CASE - Transit Case - Water-tight hard case with rollers for Fluke 1750 and Fluke 1760
CS1750 - Carry Bag for 1750; Rugged, canvas bag for monitor with pockets for accessories.
HP IPAQ 2490 - Additional Wireless Interface PDA for Fluke 1750
FLUKE-1750/MC - Additional 512Mb SD Memory Card for Fluke 1750

Technical Specifications
Power quality measurement standards
Conformance IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459
Clock/calendar Leap years, 2 4-hour clock
Real-time clock accuracy Not more than ± 1 s/day
Internal memory capacity for data At least 1 GB
Maximum recording period At least 31 days
Measurement time control Automatic
Maximum number of events Limited only by the size of the internal memory
Power requirements 100 to 2 40 V rms ± 10 %, 47-63 Hz, 40 W
Operating time during interruptions (internal UPS operation) 5 minutes per interruption, 60 minutes total operating time without recharging
Dimensions 215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)
Mass (weight) 6.3 kg (14 lb)
Input
Measurement types One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
Input channels Voltage: 4 channels, ac/dc

Current: 5 channels
Voltage channels Input resistance: 2 MΩ

Input capacitance: < 2 0 pF
Current input characteristics 2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
Measuring method Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
Synchronization and sampling
PLL-synchronization source The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
PLL lock range 42.5 to 69 Hz
Sampling frequency Voltage and current: 2 56 samples/cycle Inter-harmonics per IEC 61000-4-7: 2 560 points/10 cycles (50 Hz), 3072 points/12 cycles (60 Hz) Transient Voltage: 5 MHz
A/D resolution Voltage and current: 2 4 bits

Transient voltage: 14 bits
Voltage and current measurements
Voltage measurement range AC voltage: 1000 V rms ± 10 % over range

DC voltage: ± 1000 V + 10 % over range
Voltage crest factor 3 or less
Current measurement range Depends on current probe used
Current crest factor 4 or less
RMS voltage
Measurement type True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
Measurement uncertainty AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms

DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
RMS current
Measurement type True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Transient voltage (impulse)
Measurement type Waveshape sampling
Full scale 8000 V pk
Sample resolution 200 nS
Measurement uncertainty ± 5 % reading ± 2 0 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)
Voltage swell (rms swell)
Measurement type True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data Amplitude and duration of swell
Measurement Same as rms voltage
Voltage dip (rms sag)
Measurement type True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data Amplitude and duration of dip or interruption
Measurement Same as rms voltage
Voltage dropout (interruption)
Measurement type Same as voltage dip
LAN interface
Connector RJ-45
Speed and type 10/100 Base-T, auto MDIX
Communications protocol TCP/IP over Ethernet
Wireless controller interface
Connection wireless (2.4 GHz radio)
Speed up to 700 kbit/second
Communications protocol Bluetooth SPP

Power Measurements
Power, battery life
Measurement type True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Frequency
Measurement range 42.5 to 69 Hz
Measurement source Same as PLL synchronization source
Measurement accuracy ± 10 mHz (10 to 110 % of range, with sine wave)
Power Factor
Measurement range 0.000 to 1.000
Measurement accuracy ± 1 digit from the calculation of each measured value (±3 digits for total)
Displacement power factor
Measurement method Calculated from the phase difference between voltage fundamental and current fundamental
Measurement range - 1.000 (leading) to + 1.000 (lagging)
Measurement accuracy ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage unbalance and phase sequence
Measurement method Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
Harmonic voltage and current
Analysis window rectangular
Analysis order 1st to 50th order
Measurement accuracy Voltage / Current: 1st to 2 0th orders: ± 0.5 % reading ± 0.2 % full scale, 2 1st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)
Measurement method IEC 61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)
Analysis window rectangular
Analysis orders 1.5 to 49.5th order
Measurement method IEC 61000-4-7

Environmental Specifications
Environmental
Operating environment Indoors or in covered area outdoors, up to 2 000 m altitude
Storage temperature and humidity -20 °C to 50 °C, 80 % RH max, non-condensing
Operating temperature and humidity 0 °C to 40 °C, 80 % RH max, non-condensing
Maximum rated working voltage
Voltage terminals 1100 V rms
Voltage durability 5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
Enclosure protection IP30 (per EN 60529)
Standards:
EMC EN 61326-1:1997+A1:1998 Class A

EN 61000-3-2:1995+A1:1998+A2:1998

EN 61000-3-3:1995
Safety EN 61010-1 2 nd Edition; 2 000

Voltage input unit: Contamination Level 2 , Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated overvoltage: 8000 V)





Novinky a zmeny