Current carrying capacity - Ampacity

Frequent question during the development of electronic cabling is "How much current can a 2,5 mm² conductor carry?" or "How thick conductor must be to carry 100 Amps safely?". Answers can be usually found in conductor datasheets where you have to look for Ampacity rating or current carrying capacity...

Frequent question during the development of electronic cabling is "How much current can a 2,5 mm² conductor carry?" or "How thick conductor must be to carry 100 Amps safely?". Answers can be usually found in conductor datasheets where you have to look for Ampacity rating or current carrying capacity.

Current carying capacity of conductors is also known as Ampacity - abbreviation of two words, ampere and capacity.

Choosing the right conductor is a complex task. There are limiting factors, such as air temperature, the ability to dissipate heat and insulation durability. You can find more details in norms IEC 60364-5-52:2009 and BS 7671:2008.

Values below are maximal allowed, it is upmost important to lower them a bit for real-world usage. We are counting with laboratory like, ideal conditions - freestanding, single conductor with PVC insulation (max 70°C), 30°C air temperature, fitting method E according to IEC 60364-5-52.

For any other air temperatures than 30°C, you need to use compensation multiplier of 1.22 for 10°C and 0,50 for air temperature 60°C. This means, at air temperatures of 60°C, it is possible to transfer just half the current.

Just like as applying temperature compensation, we need to apply compensation for having multiple wires next to each other or having multi-core wires, as well as compensating for thermally insulating surroundings which do not allow self-cooling of the wires. During calculations, we also have to count with voltage drop, because this shows us the value of power loss which is then translated to temperature radiation. If we use a multistrand wire lead, most if the time the diameter (multistrand wires have larger core diameter while having the same effective cross section as solid core cables) and parameters for harmonic frequencies changes. 

ampacita Cu vodiča

Graph: Current carrying capacity of copper coductors.

Table of maximum theoretical current carrying capacity of copper conductors.

cross section
(mm² Cu)
max. current
(A)
max. current
(A) three conductors
voltage drop
(mV / A / m)
total voltage drop
at max. load
(mV / m)
core diameter
(mm)
1 19 44 836 1,1
1,5 26 17,5 29 754 1,4
2,5 36 24 18 648 1,8
4 47 32 11 517 2,3
6 60 41 7,3 438 2,8
10 82 57 4,4 361 3,6
16 109 76 2,8 305 4,5
25 142 96 1,75 249 5,6
35 174 119 1,25 218 6,7
50 215 144 0,93 200 8,0
70 264 184 0,63 166 9,4
95 317 223 0,46 146 11,0
120 364 259 0,36 131 12,4
150 416 299 0,29 121 13,8
185 472 341 0,23 109 15,3
240 552 403 0,18 99 17,5
300 650 464 0,145 94 19,5
400 754 0,105 79 22,6
500 868 0,086 75 25,2
630 1005 0,068 68 28,3
800 1150 0,053 61 31,9
1000 1310 0,042 55 35,7

Related products

Marián Hubinský

Elso Philips Service s.r o,
Jilemnického 2/53
91101 Trenčín

Tel.:+421 32 6582410

e-mail: elso@elso.sk

Product added to compare.

Webové stránky spoločnosti Elso Philips Service používajú súbory cookies na svoju správnu funkciu a pre zabezpečenie lepších služieb pre Vás.